Qualitative Analysis of Performance Degradation in the ARCA Pneumatic Emergency Blow-off Valve at the Sarcheshmeh Copper Complex Oxygen Plant: A Case Study of the Role of the Positioner, Instrument Air Quality, and Environmental Conditions in Pressure Stability
Qualitative Analysis of Performance Degradation in the ARCA Pneumatic Emergency Blow-off Valve at the Sarcheshmeh Copper Complex Oxygen Plant: A Case Study of the Role of the Positioner, Instrument Air Quality, and Environmental Conditions in Pressure Stability
Masoud Hajizadeh1
1) National Iranian Copper Industries Company, Sarcheshmeh, Rafsanjan Oxygen Plants, Instrumentation Maintenance Unit
IOI Code
:
AAHD-ABKBKE
Publication :
National Conference on Information Technology, Nanotechnology, Artificial Intelligence and Technological Futures Studies(itnaf.ir)
Abstract :
This article adopts a qualitative-analytical approach to examine the performance degradation of the ARCA pneumatic emergency blow-off valve at the Sarcheshmeh Copper Complex oxygen plant as an issue extending beyond a localized equipment defect. The central problem of the study is how positioner malfunction, deterioration of instrument air quality, contamination of pneumatic passages, wear of actuator components, and harsh environmental conditions interact to reduce the reliability of the emergency blow-off system. The findings indicate that valve degradation first emerges at the technical-root level through calibration error, stiction, internal leakage, and contamination of the control-air path, and subsequently becomes visible in operational indicators such as increased response time, increased hysteresis, pressure fluctuation, and abnormal instrument air consumption. The analysis shows that the ARCA blow-off valve should not be regarded merely as an isolated maintenance item; rather, it must be understood as part of the pressure-protection architecture and process-stability framework of oxygen production. Accordingly, the article concludes that maintaining the reliability of this system requires a transition from reactive and time-based maintenance toward condition-based maintenance, DCS data monitoring, instrument air quality control, regular positioner calibration, hysteresis testing, and periodic functional testing.
Keywords : arca blow off valve pneumatic positioner instrument air pressure stability condition based maintenance