optimal locating of unified power quality conditioner based on phase angel control by considering seasonal load

optimal locating of unified power quality conditioner based on phase angel control by considering seasonal load

mehrdad parsa1 alireza moradi2

1) Masters, Islamic Azad University, damghan branch, iran
2) Member of the academic staff,Islamic Azad University, mahdishahr branch, iran

IOI Code : XAAB-BGKFD
Publication : The 3rd International Conference on Engineering Sciences and Technology(3icoesat.com)
Abstract :
    In this article, a multi-objective planning is demonstrated for reactive power compensation in radial distribution networks with Seasonal load via unified power quality conditioner (UPQC). UPQC model, based on phase angle control (PAC), is used. In the proposed approach, the optimal location, the optimal reactive power compensation required at the location, and the optimal design parameters of UPQC are determined by minimizing three objective functions: 1) the rating of UPQC, 2) network power loss, and 3) percentage of nodes with under voltage problem. These objectives are simultaneously minimized to obtain a set of non-dominated solutions using multi-objective PSO (MOPSO).In order to evaluate reliability of mentioned approach, simulation is done on 33-bus distribution network.

Keywords : mopso radial distribution network reactive power compensation unified power quality conditioner (upqc