Fault Location on High Voltage Direct Current Using Hybrid Method

Fault Location on High Voltage Direct Current Using Hybrid Method

Mohammad Daisy1 Shahram Javadi2

1) Power System Lab Azad university Tehran central branch, Tehran, Iran,
2) Power System Lab Azad university Tehran central branch, Tehran, Iran,

IOI Code : XAEK-CEAZG
Publication : The National Conference on Recent Advances in Engineering and Modern Sciences(desconf.com)
Abstract :
    Detecting exact fault location in a HVDC system is necessary for fast recovery of the system to increase reliability and performance. This paper presents a novel method based on a hybrid intelligent algorithm for determining fault location in voltage source converter-high voltage direct current (VSC-HVDC) systems. This method measures frequency, energy and time and employs Hilbert-Huang Transform (HHT) to obtain fault features. Time delay, characteristic frequency, energy contraction and high frequency energy are used as support vector regression to obtain fault location in the system. Then, Bat algorithm (BA) optimizes model parameters through mutual validation compared to other algorithms. High frequency variance contribution rate (HVCR) is used to detect fault location. VSC-HVDC system is simulated to verify reliability of the system and evaluate the proposed method. Results showed that the proposed method obtains proper reliability and accuracy in hybrid transmission systems with low data.

Keywords :