The process of removing phosphorus from municipal wastewater by electrolysis Case study: Tabriz city sewage
The process of removing phosphorus from municipal wastewater by electrolysis Case study: Tabriz city sewage
Amirhassan Talebi1
1) Director of Energy Group, Water and Wastewater Co., East Azarbaijan
IOI Code
:
XDHH-GFHAD
Publication :
5th.International Conference & 6th.National Conference on Civil Engineering, Architecture, Art and Urban Design(5iccacs.ir)
Abstract :
The purpose of this study was to investigate the efficiency of electrolysis method to remove phosphorus from wastewater treatment plants. Although primary and secondary treatment processes when completed with disinfection (conventional wastewater treatment) can remove 85% of BOD and suspended solids and almost all pathogens, some contaminants such as nitrogen, phosphorus, soluble COD and Heavy metals are removed to a lesser extent. This is a major problem, especially when large amounts of treated wastewater are discharged into a low-flow surface water stream or sensitive ecosystem.
In the present study, with consecutive sampling during 30 days and at different hours, 60 samples were tested and analyzed according to the usual standards by sampling method from the effluent of Tabriz wastewater treatment plant. After determining the quality of raw wastewater, this effluent was treated by electrolysis with aluminum plates at different pH, voltage and times. Process efficiency was evaluated for COD, dye, phosphate and surfactant removal.
The results show that all initial concentrations of organic phosphorus remaining after the electrochemical process with a constant current of 0.6 amps, reached less than 1 mg / l in fifty minutes. Also, the removal efficiency of organic phosphorus with different initial concentrations during the reaction time for sixty minutes was between 92.10 to 97.50%.
Keywords : phosphorus electrocoagulation aluminum plate effluent tabriz wastewater treatment plant