Line outage contingency analysis including the system islanding scenario
Line outage contingency analysis including the system islanding scenario
amin eskandari dehkordi1
1) Islamic Azad University, Science and Research Branch, Hamedan,
IOI Code
:
XYAH-ZDAGA
Publication :
3rd international conference of Science and Engineering(3icesconf.com)
Abstract :
The paper describes an algorithm for determining the line outage contingency of a line taking into account of line over load effect in remaining
lines and subsequent tripping of over loaded line(s) leading to possible system split or islanding of a power system. The optimally ordered sparse
[B0], [B00] matrices for the integrated system are used for load flow analysis to determine modified values of voltage phase angles [d] and bus
voltages [V] to determine the over loading effect on the remaining lines due to outage of a selected line outage contingency. In case of over loading
in remaining line(s), the over loaded lines are removed from the system and a topology processor is used to find the islands. A fast decoupled load
flow (FDLF) analysis is carried out for finding out the system variables for the islanded (or single island) system by incorporating appropriate
modification in the [B0] and [B00] matrices of the integrated system. Line outage indices based on line overload, loss of load, loss of generation and
static voltage stability are computed to indicate severity of a line outage of a selected line.
Keywords : contingency line outage rotating mass system islanding