fault detection during power swing with an algoritm based on wavelet transform
fault detection during power swing with an algoritm based on wavelet transform
amirreza mehri1 kazem mazlumi2
1) master of science student in power engineering,university of
2) Associate professor in faculty of engineering,university of
IOI Code
:
XYCB-ABAHF
Publication :
1st International Congress on Engineering Innovation and Development of Technology(iceiconf.ir)
Abstract :
when a power swing takes place, the apparent impedance measured by a distance relay may move away from the normal load area into the distance relay operating zones.this may cause unintended trip. to ensure the security of operation, most modern distance relays detect and block the operation during power swing. If a fault during power swing, distance relay should be able to detect the fault and operate correctly. In that case it is necessary to unblock the relay during power swing. In this paper a new technique based on wavelet transform is using for detecting fault. It is shown that, this technique improves the performance of fault detection by employing the absolute sum value of third level in DWT and proposed algoritm.
Keywords : fault detection power swing distance relay wavelet transform