Distance Protection Double-Circuit Parallel Lines for inter-circuit faults
Distance Protection Double-Circuit Parallel Lines for inter-circuit faults
esmail sari1
1) Shahid Chamran University of Ahvaz
IOI Code
:
XYCZ-AACKG
Publication :
International Conference on Engineering and Applied Science(iceasconf.com)
Abstract :
Double-circuit Parallel transmission lines with one tower create unique problems for distance relay especially when inter-circuit faults happen. in this paper a new algorithm for distance protection double-circuit parallel presented. The algorithm calculates the fault impedance using one end sampling voltages and currents from a single line. The theoretical basis of the proposed algorithm is symmetrical component of double circuit parallel transmission lines. with this way mutual coupling between the lines disappear and we try find relation between zero sequence component current between the two circuit. The simulations show that the proposed algorithm can obtain the accurate fault reactance when cross-country bolted faults occur, which is superior to the existing distance protection algorithm based on one-end data from a single line. In this thesis, PSCAD/EMTDC software and MATLAB have been used for simulation.
Keywords : distance protection double circuit transmission lines inter circuit faults