The impact of the AVR to the planning and management of sub-synchronous resonance in power systems
The impact of the AVR to the planning and management of sub-synchronous resonance in power systems
Meysam Saeedi Rad1 Gholamreza Safarnejad2 Amir Dalvand3
1) Lecturer, Faculty of Engineering, Islamic Azad University Andimesh
2) PhD in Agricultural Engineering, Structural Engineering Aby.mdrs Azad University Andimesh, CEO of the dam and powerhouse Venus and surgical
3) PhD Astratzhyk.mdrs Azad University Andymeshk and vice dam and powerhouse Venus and surgical
IOI Code
:
XYDK-AHZGB
Publication :
International Conference On Research Science And Technology(restconf.com)
Abstract :
In this paper the effect of the automatic voltage regulator (AVR) on the following division synchronous resonance (SSR) systems can be studied. Parameters can be divided, the compensation factor. Divisions Hopf, where a pair of complex conjugate eigenvalues of the linear model operating point, the left side to the right side in the complex plane, in the interest of all AVR is detected. Split Point Hopf s proof that areas with stable operating point, by the amount of interest placed AVR. Hopf dividing point spatial variation as a function of the AVR for two of the working conditions have been obtained. Time-domain simulation results based on the mathematical model of nonlinear dynamics in different and various amounts of compensation coefficients AVR agreed with the values obtained from the analysis division.
Keywords : automatic regulators under synchronization complex value