Studying Cooling Water Exchanger and Three-Stage Compressor using Aspen Plus and Aspen B-Jac

Studying Cooling Water Exchanger and Three-Stage Compressor using Aspen Plus and Aspen B-Jac

Mehrdad Ghanavatian1 Aziz Azimi2

IOI Code : XYZG-ZAAKA
Publication : 2nd International Conference on Science and Engineering(2icesconf.com)
Abstract :
    This paper aims at examining the causes of poor performance of a cooling water exchanger in summer with the temperature and humidity increasing while it was designed to cool the air emitting from the main compressors of air separation unit. The data obtained from the cooling water exchanger of the air department of Fajr Petrochemical Company using Aspen B-Jac, which was designed by the English reputable company of Air Product, were compared with the experimental data and the results indicated an appropriate conformity with the main sample. The results obtained from the employed software show that the exchanger has no problem and the problem is related to the intermediate compressors of the main compressors. Poor performance of the water cooling exchanger is due to the additional water (high humidity). The additional water has been formed due to the poor performance of the 3-stage intermediate compressor.

Keywords : cooling water exchanger 3 stage compressor humidity