Abstract :
    This article examines the best evaporator operating temperature for one refrigerant, which reduces the number of tubes used in the evaporator and is economically viable. The HTRI software used in this article is to determine the number of evaporator tubes. The amount of overdesign is considered to be 20%. The evaporator capacity in question for the chiller is 50 tons of single circuit. Finally, we find that the temperature of 2° C is the optimal state, which reduces both the size and number of evaporators. Where the refrigerant speed reaches its lowest point between two temperatures of 1 and 2.5 degrees Celsius. Because when the refrigerant speed in turbulent flow decreases, the refrigerant has more time to transfer heat.

Keywords : optimization shell and tube dx temperature htri