A Multiple DGs Islanding Detection Method Base on The DWT and THD of Current
A Multiple DGs Islanding Detection Method Base on The DWT and THD of Current
Amir Hossein Kimiai Asadi1 Hasan Meyar Naeimi2 Alireza Jahangiri3
1) Department of Electric Engineering, Hamedan Branch, Islamic Azad University, Hamedan,Iran
2) Department of Electric Engineering, Hamedan Branch, Islamic Azad University,Hamedan,Iran
3) Department of Electric Engineering, Hamedan Branch, Islamic Azad University,Hamedan,Iran
IOI Code
:
XYDC-AFGFA
Publication :
International Conference on Researches in Science & Engineering(icrsie.com)
Abstract :
According to the IEEE standards 1547-2003 Islanding concept is a condition in which a portion of the utility system that contains both loads and Distributed Generation (DG) remains energized while isolated from the remainder of the utility system and in this condition DG must be disconnected at most within 2 seconds. Generally, if there are large changes in loading for DG after loss of the main power supply, then islanding conditions are easily detected by monitoring several parameters: voltage magnitude, phase displacement and frequency change. However, in case of small changes in loading for DG, the conventional methods have some difficulty in detecting such a particular islanding condition. Therefore, propose of this paper is, fast and accurate method for Multiple Distributed Generation (MDGs) islanding detection in the distribution networks based on THD of current and analysis of DG transient terminal unbalance voltage by using Discrete Wavelet Transform (DWT) and Daubechies mother wavelet. For any possible event in the distribution network such as : islanding and non islanding (Normal utilization, Faults include 3-ph, 2-ph, 2-ph to ground, 1-ph to ground in all buses, Load switching, DG switching, Capacitor banks switching) conditions with employing of DWT, requirement features by the third level of decomposition classified and accordingly events divided two groups islanding and non islanding. Performance of proposed method tested on IEEE 13 Node Test Feeder in three scenario include ground fault, load rejection and capacitor bank switching. This system have two different types of DGs that are synchrounous and induction generators. The PSCAD/EMTDC sued to simulate the different scenarios studied and analyzing to be optimized in progress of indices such as: accuracy, speed and reliability. By evaluation, it was determined that proposed method compared with conventional islanding detection method is able to islanding detecting in presence of MDG with high speed and high accuracy.
Keywords : islanding detection discrete wavelet transform (dwt) unbalance voltage total harmonic distortion (thd) of current multiple distributed generation (mdg)