providing a compound test procedure to verify protection settings of generator
providing a compound test procedure to verify protection settings of generator
behrooz shoghi motlagh1 jalal sahebkar farkhani2
1) master power electric engineer of Azarakhsh power transmission company(moham shargh group)
2) master power electric engineer of Azarakhsh power transmission company(mohamshargh group)
IOI Code
:
XYEC-BAHHC
Publication :
The 4th International Conference on Engineering and Applied Sciences(4iceasconf.com)
Abstract :
For the reliability of a power system, protection of the generator is essential. Generator is the most important and costly equipment in the complete power system setup. In this paper, a compound method is used to verify the generator protection relay performance. A steam power plant unit of Shariati which has ABB REG*316 relay, has been used as a case study. In this method, the accuracy and performance of relay settings in the situation of short circuit and transient automatically checked. For this purpose, fault conditions in the power system simulated by PSCAD software, then this result was transferred to test device (omicron) through Comtrade format. The test device is able to convert these inputs to voltage and current waveforms for testing in real situation fault. As a result, the values of voltage and current waveforms generated by the test device injection to relay, the settings and accuracy of relay were investigated.
Keywords : generator numerical management relay omicron device tester protection function